Datacenter Features


Built-up Area

  • 35000 sq ft Tier III+ Datacenter, with 99.982% availability
  • Tiering Specification as per Uptime Institute
  • LEED benchmark design and build

Power

  • Dual power supply of 3750 KVA from Utility
  • 150 W per sq ft, Fully redundant PDU’s, 2N UPS configuration
  • 2x2MW (N+1) Diesel Generators with 24 hr fuel storage

Rack Power

  • 3.75 KW power per rack
  • Dual feed to racks
  • Option of having 20 or 30 Amps

Cooling

  • Air based cooling plant, Fully redundant CRAH units
  • N+1 Air cooled chillers with free cooling
  • N+1 Chilled Glycol Pumps with VFD Controls

Fire Detection & Suppression

  • VESDA, installed in under raised floor, Both heat and smoke detection
  • FM 200 based suppression system, Pre-action sprinkler based installed over racks, Sprinkler system – both flooded and pre action

Architecture

  • Large column bays (30x50 feet)
  • Minimum floor to ceiling clearances — 18 feet from structural slab to lowest structural member

Raised floor

  • Total raised floor area of 20000 sq ft
  • Raised floor 36-inch
  • Floor loading: 1250 lbs per tile

Build Room

  • Available for system acclimatization or build

Networks

  • Diverse Telco Entrances with De-marcs – North & South

Physical and IT Security

  • External and Internal; CCTV monitoring and surveillance
  • Proximity card readers, 24x7 manned security
  • Building Monitoring System